Horário de atendimento: Segunda a sexta, das 9h às 18h.
F-MS 2200/30 ST - F-MS 2200/30 ST 2805392 PHOENIX CONTACT Type 2 surge protection plug
Em estoque Produto em alta

F-MS 2200/30 ST

F-MS 2200/30 ST 2805392 PHOENIX CONTACT Type 2 surge protection plug

$0.00 USD
4037 em estoque
Especificações principais
GTIN: 4046356446419
Note: Made to Order (non-returnable)
Orderkey: 2805392
(General): VSDC> 2200 V
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
GTIN 4046356446419
Note Made to Order (non-returnable)
Orderkey 2805392
(General) VSDC> 2200 V
Catalog page Page 56 (C-4-2017)
Packing unit 10 pc
Country of origin DE (Germany)
(Connection data) EN 61643-11 2012
Custom tariff number 85363010
(Ambient conditions) T2
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Minimum order quantity 10 pc
Type (Ambient conditions) DIN rail module, two-section, divisible
(Additional descriptions) ≤ 0.1 kV (at 3 kA)
Color (Ambient conditions) jet black RAL 9005
Depth (Key Commercial Data) 55.3 mm
Width (Key Commercial Data) 17.5 mm
(Standards and Regulations) No hazardous substances above threshold values
EN type (Ambient conditions) T2
Height (Key Commercial Data) 52.4 mm
Shock (operation) (Dimensions) 25g
Degree of protection (Dimensions) IP20
Mounting type (Ambient conditions) on base element
Vibration (operation) (Dimensions) 5g
Weight per Piece (excluding packing) 37.200 g
Housing material (Ambient conditions) PA 6.6
China RoHS (Standards and Regulations) Environmentally friendly use period: unlimited = EFUP-e
Connection method (Protective circuit) pluggable
Horizontal pitch (Key Commercial Data) 1 Div.
Mode of protection (Ambient conditions) L-PE
Standards/regulations (Connection data) IEC 61643-11 2011
Degree of pollution (Ambient conditions) 3
Number of positions (Ambient conditions) 1
Response time tA (Additional descriptions) ≤ 100 ns
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC test classification (Ambient conditions) II
TOV behavior at UT (Additional descriptions) 1550 V AC (200 ms / withstand mode)
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Nominal frequency fN (Additional descriptions) 50 Hz
Residual current IPE (Additional descriptions) ≤ 3 µA
Residual voltage Ures (Additional descriptions) ≤ 0.4 kV (at In)
Surge protection fault message (Ambient conditions) optical
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Voltage protection level Up (Additional descriptions) ≤ 5 kV
Flammability rating according to UL 94 (Ambient conditions) V-0
Short-circuit current rating ISCCR (Additional descriptions) 25 kA
Distance between live and grounded parts (Ambient conditions) 8 mm
Nominal discharge current In(8/20) µs (Additional descriptions) 15 kA
Maximum discharge current Imax(8/20) µs (Additional descriptions) 30 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs (Additional descriptions) ≤ 5 kV

Descrição do produto

Plug protection. Type 2 surge arrester, arc arrester with insulation resistance, use only as plug protection. replacement for art. corresponding complete.
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação