Horário de atendimento: Segunda a sexta, das 9h às 18h.
MCR-SL-S-200-U - MCR-SL-S-200-U 2813460 PHOENIX CONTACT Current transducers
Em estoque Produto em alta

MCR-SL-S-200-U

MCR-SL-S-200-U 2813460 PHOENIX CONTACT Current transducers

$0.00 USD
4749 em estoque
Especificações principais
: 0 A AC ... 150 A AC
Color: green (RAL 6021)
Depth: 70.5 mm
Width: 55 mm
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
0 A AC ... 150 A AC
Color green (RAL 6021)
Depth 70.5 mm
Width 55 mm
Height 85 mm
Diameter ≤ 18.5 mm
Curve type Sinusoidal and non-sinusoidal
Certificate CE-compliant
Product type Current transducer
Screw thread M3
Mounting type DIN rail mounting
Identification UL/C-UL Listed UL 508
Surge strength Depending on through connected conductor
Article revision 03
Housing material Polyamide PA non-reinforced
Pollution degree 2
Stripping length 8 mm
Connection method Screw connection
Mounting position any
Operate threshold 1 % (of final value)
Overload capacity Depending on laid conductor
Tightening torque 0.5 Nm ... 0.6 Nm (4,4 ... 5,31 lbf-in.)
Input current range 0 A AC ... 100 A AC
Current input signal 0 A ... 200 A
Degree of protection IP20
Overvoltage category III
Supply voltage range 20 V DC ... 30 V DC
Voltage output signal 0 V ... 5 V
Nominal supply voltage 24 V DC
Step response (10-90%) < 340 ms
Max. current consumption < 30 mA
Rated insulation voltage 300 V AC (to earth)
Configurable/programmable Yes
Frequency measuring range 30 Hz ... 6000 Hz
Test voltage input/output 4.13 kV AC (50 Hz, 60 s)
Max. voltage output signal (0 V ... 10 V) 14 V, (0 V ... 5 V) 7 V
Maximum transmission error < 1 % (of final value)
Conductor cross section AWG 24 ... 14
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Ambient temperature (operation) -20 °C ... 60 °C
Load/output load voltage output ≥ 10 kΩ
Maximum temperature coefficient < 0.035 %/K
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Setting range for max. input current 0 A AC ... 200 A AC
Setting range for min. input current 0 A AC ... 100 A AC
Maximum power dissipation for nominal condition 1 W

Descrição do produto

MCR current converter, for measuring sinusoidal and non-sinusoidal alternating currents, input current 0...200 A, output voltage 0... (5) 10 V
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top