Horário de atendimento: Segunda a sexta, das 9h às 18h.
TRIO-PS-2G/1AC/24DC/5/B+D - TRIO-PS-2G/1AC/24DC/5/B+D 2903144 PHOENIX CONTACT Power supply unit
Em estoque Produto em alta

TRIO-PS-2G/1AC/24DC/5/B+D

TRIO-PS-2G/1AC/24DC/5/B+D 2903144 PHOENIX CONTACT Power supply unit

$0.00 USD
4184 em estoque
Especificações principais
GTIN: 4046356726955
Orderkey: 2903144
Catalog page: Page 219 (C-4-2017)
Packing unit: 1 pc
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
GTIN 4046356726955
Orderkey 2903144
Catalog page Page 219 (C-4-2017)
Packing unit 1 pc
(Input data)
(Output data) > 900000 h (60 °C)
Country of origin CN (China)
Custom tariff number 85044030
(Ambient conditions) typ. 100 ms (230 V AC)
Derating (Input data) > 60 °C ... 70 °C (2.5%/K)
Efficiency (Output data) > 89 % (for 230 V AC and nominal values)
Net weight (Output data) 0.45 kg
Output power (Input data) 120 W
Stripping length (General) 10 mm
Climatic class (Dimensions) 3K3 (in acc. with EN 60721)
Connection method (General) Push-in connection
Depth (Key Commercial Data) 115 mm
Width (Key Commercial Data) 35 mm
Height (Key Commercial Data) 130 mm
Residual ripple (Input data) < 50 mVPP(with nominal values)
Control deviation (Input data) < 1 % (change in load, static 10 % ... 90 %)
Protection class (Output data) II (in closed control cabinet)
Input fuse (Ambient conditions) 6.3 A (internal (device protection))
Mounting position (Output data) horizontal DIN rail NS 35, EN 60715
(Connection data for signaling) 15 Hz ... 150 Hz, 4g, 90 min.
Degree of pollution (Dimensions) 2
Feedback resistance (Input data) ≤ 35 V DC
Installation height (Dimensions) ≤ 5000 m (> 2000 m, observe derating)
Connection in series (Input data) yes
Degree of protection (Dimensions) IP20
Degree of protection (Output data) IP20
Typical response time (Input data) < 1 s
Assembly instructions (Output data) alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Connection in parallel (Input data) Yes, for redundancy and increased capacity
Nominal output voltage (Input data) 24 V DC ±1 %
Mains buffering (Ambient conditions) typ. 20 ms (120 V AC)
Weight per Piece (excluding packing) 572.840 g
Shock (Connection data for signaling) 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
REACh SVHC (Standards and Regulations) Lead 7439-92-1
AC frequency range (Ambient conditions) 50 Hz ... 60 Hz ±5 Hz
Dynamic Boost (IDyn.Boost) (Input data) 7.5 A (5 s)
Type of protection (Ambient conditions) Transient surge protection
Voltage (Connection data for signaling) 10 V (Test Level 3)
Comments (Connection data for signaling) Criterion B
Current consumption (Ambient conditions) 2.2 A (100 V AC)
Input voltage range (Ambient conditions) 100 V AC ... 240 V AC -15 % ... +10 %
MTBF (IEC 61709, SN 29500) (Output data) > 3380000 h (25 °C)
Nominal output current (IN) (Input data) 5 A
Inrush surge current (Ambient conditions) ≤ 16 A (typical)
Power loss nominal load max. (Input data) < 16 W
Stripping length (Connection data, input) 8 mm
Conductor cross section AWG max. (General) 12
Conductor cross section AWG min. (General) 24
Connection method (Connection data, input) Push-in connection
Stripping length (Connection data, output) 8 mm
Connection method (Connection data, output) Push-in connection
Power factor (cos phi) (Ambient conditions) 0.5
Ambient temperature (operation) (Dimensions) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Conductor cross section solid max. (General) 4 mm²
Conductor cross section solid min. (General) 0.2 mm²
Discharge current to PE (Ambient conditions) < 0.25 mA
UL approvals (Connection data for signaling) UL Listed UL 508
Insulation voltage input/output (Output data) 3 kV AC (type test)
Noise emission (Connection data for signaling) EN 55011 (EN 55022)
Noise immunity (Connection data for signaling) EN 61000-6-2:2005
Nominal power consumption (Ambient conditions) 272 VA
Conductor cross section flexible max. (General) 2.5 mm²
Conductor cross section flexible min. (General) 0.2 mm²
Frequency range (Connection data for signaling) 0.15 MHz ... 80 MHz
Dielectric strength maximum (Ambient conditions) ≤ 300 V AC 15 s
Nominal input voltage range (Ambient conditions) 100 V AC ... 240 V AC
Contact discharge (Connection data for signaling) 4 kV (Test Level 2)
Protective circuit/component (Ambient conditions) Varistor
Rail applications (Connection data for signaling) EN 50121-4
Test field strength (Connection data for signaling) 3 V/m (Test Level 2)
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 85 °C
Low Voltage Directive (Connection data for signaling) Conformance with LV directive 2006/95/EC
Shipbuilding approval (Connection data for signaling) DNV GL (EMC A)
Standards/regulations (Connection data for signaling) EN 61000-6-3
Vibration (operation) (Connection data for signaling) < 25 Hz, amplitude ±1.6 mm (according to DNV GL CG-0339)
Setting range of the output voltage (USet) (Input data) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Choice of suitable circuit breakers (Ambient conditions) 6 A ... 16 A (Characteristics B, C, D, K)
Conductor cross section AWG max. (Connection data, input) 12
Conductor cross section AWG min. (Connection data, input) 24
Standard - Safe isolation (Connection data for signaling) DIN VDE 0100-410
Conductor cross section AWG max. (Connection data, output) 16
Conductor cross section AWG min. (Connection data, output) 24
Conductor cross section solid max. (Connection data, input) 4 mm²
Conductor cross section solid min. (Connection data, input) 0.2 mm²
Max. permissible relative humidity (operation) (Dimensions) ≤ 95 % (at 25 °C, non-condensing)
Maximum power dissipation in no-load condition (Input data) < 1 W
Protection against surge voltage on the output (Input data) ≤ 30 V DC
Conductor cross section solid max. (Connection data, output) 1.5 mm²
Conductor cross section solid min. (Connection data, output) 0.2 mm²
Standard - Electrical safety (Connection data for signaling) IEC 60950-1/VDE 0805 (SELV)
Electromagnetic compatibility (Connection data for signaling) Conformance with EMC Directive 2014/30/EU
Conductor cross section flexible max. (Connection data, input) 2.5 mm²
Conductor cross section flexible min. (Connection data, input) 0.2 mm²
Conductor cross section flexible max. (Connection data, output) 1.5 mm²
Conductor cross section flexible min. (Connection data, output) 0.2 mm²
Standard - Safety of transformers (Connection data for signaling) EN 61558-2-16 (air clearances and creepage distances only)
Standard – Safety extra-low voltage (Connection data for signaling) IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard – Limitation of mains harmonic currents (Connection data for signaling) EN 61000-3-2
Approval - requirement of the semiconductor industry with regard to mains voltage dips (Connection data for signaling) Semi F47-0706
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data for signaling) EN 50178/VDE 0160 (PELV)

Descrição do produto

TRIO POWER primary switching power supply with push-in connection for rail mounting, input: single-phase, output: 24 V DC/5 A
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top