Especificações principais
: C2
Note: 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Type: DIN rail module, one-piece
Color: gray (RAL 7042)
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
C2
Note 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Type DIN rail module, one-piece
Color gray (RAL 7042)
Depth 83.5 mm (incl. DIN rail 7.5 mm)
Width 6.2 mm +0.1 mm
Height 105.8 mm
Altitude ≤ 4000 m (amsl)
Product type Surge protection for MCR technology
Screw thread M3
Mounting type DIN rail: TH 35 - 7.5 mm
Rated current 6 A (55 °C)
Product family TERMITRAB complete
Open side panel No
Article revision 03
Housing material PBT
Pollution degree 2
Connection method Screw connection
Tightening torque 0.5 Nm ... 0.6 Nm
Nominal voltage UN 24 V DC
Dimensional drawing
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Insulating material PBT
Resistance per path ≤ 100 mΩ
Degree of protection IP20
Overvoltage category III
Residual current IPE ≤ 1 µA
Capacity (Core-Earth) typ. 2.2 nF
IEC test classification C1
Standards/specifications IEC 61643-21
Input attenuation aE, sym. typ. 0.3 dB (≤ 300 kHz / 150 Ω)
Max. required back-up fuse 6.3 A (FF)
Conductor cross section AWG 24 ... 12
Response time tA(line-line) ≤ 1 ns
Response time tA(line-earth) ≤ 100 ns
Conductor cross section rigid 0.2 mm² ... 4 mm²
Maximum continuous voltage UC 30 V DC
Pulse reset time (line-earth) ≤ 40 ms
Impulse durability (line-line) C1 - 1 kV / 500 A
Surge protection fault message optical
Ambient temperature (operation) -40 °C ... 85 °C
Impulse durability (line-earth) C1 - 1 kV / 500 A
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Permissible humidity (operation) 5 % ... 95 %
Operating effective current ICat UC ≤ 5 µA
Flammability rating according to UL 94 V-0
Voltage protection level Up(line-line) ≤ 50 V (C1 - 1 kV / 500 A)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Voltage protection level Up(line-earth) ≤ 1.35 kV (C1 - 1 kV / 500 A)
Total discharge current Itotal(8/20) µs 5 kA
Nominal discharge current In(8/20) µs (line-line) 0.5 kA
Cut-off frequency fg (3 dB), sym. in 150 Ω system typ. 1 MHz
Nominal discharge current In(8/20) µs (line-ground) 5 kA
Pulse discharge current Iimp(10/350) µs (line-earth) 0.5 kA

Descrição do produto

Surge protection with integrated status indication for a potential-free 2-wire signal circuit with high rated current.