Horário de atendimento: Segunda a sexta, das 9h às 18h.
TTC-6P-3-24DC-PT-I - TTC-6P-3-24DC-PT-I 1061383 PHOENIX CONTACT Surge protection, consisting of protective plug and base element,..
Em estoque Produto em alta

TTC-6P-3-24DC-PT-I

TTC-6P-3-24DC-PT-I 1061383 PHOENIX CONTACT Surge protection, consisting of protective plug and base element,..

$0.00 USD
3946 em estoque
Especificações principais
GTIN: 4055626715742
Orderkey: 1061383
(General): D1 - 500 A
(Drawings):
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
GTIN 4055626715742
Orderkey 1061383
(General) D1 - 500 A
(Drawings)
Catalog page Page 143 (C-4-2019)
Packing unit 1 pc
Depth (Drawings) 100 mm (incl. DIN rail 7.5 mm)
Width (Drawings) 6.2 mm +0.1 mm
Country of origin DE (Germany)
ETIM 5.0 (eCl@ss) EC000943
ETIM 6.0 (eCl@ss) EC000943
ETIM 7.0 (eCl@ss) EC000943
Height (Drawings) 105.8 mm
(Connection data) EN 61643-21 2001 + A1:2009 + A2:2013
Custom tariff number 85363010
(Ambient conditions) light grey RAL 7035
Altitude (Dimensions) ≤ 4000 m (amsl (above mean sea level))
Rated current (General) 5 A (55 °C)
Type (Ambient conditions) DIN rail module, two-section, divisible
Color (Ambient conditions) traffic grey A RAL 7042
(Standards and Regulations) For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Nominal voltage UN (General) 24 V DC
eCl@ss 8.0 (Classifications) 27130807
eCl@ss 9.0 (Classifications) 27130807
Resistance per path (General) < 0.1 Ω
Capacity (line-line) (General) typ. 30 pF
Dimensional drawing (Drawings)
Residual current IPE (General) ≤ 1 µA
Capacity (line-earth) (General) typ. 30 pF
Degree of protection (Dimensions) IP20
IEC test classification (General) C1
Mounting type (Ambient conditions) DIN rail: TH 35 - 7.5 mm
Input attenuation aE, sym. (General) typ. 0.3 dB (≤ 12 MHz / 150 Ω)
Max. required back-up fuse (General) 5 A (F)
Weight per Piece (excluding packing) 0.000 g
Housing material (Ambient conditions) PBT
Response time tA(line-line) (General) ≤ 1 ns
Stripping length (Protective circuit) 8 mm
China RoHS (Standards and Regulations) Environmentally Friendly Use Period = 50
Connection method (Protective circuit) Push-in connection
Pulse reset time (line-line) (General) ≤ 30 ms
REACh SVHC (Standards and Regulations) Lead 7439-92-1
Response time tA(line-earth) (General) ≤ 100 ns
Maximum continuous voltage UC (General) 30 V DC
Pulse reset time (line-earth) (General) ≤ 500 ms
Direction of action (Ambient conditions) Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Impulse durability (line-line) (General) C1 - 1 kV / 500 A
Impulse durability (line-earth) (General) C1 - 1 kV / 500 A
Standards/specifications (Connection data) IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Ambient temperature (operation) (Dimensions) -40 °C ... 85 °C
Operating effective current ICat UC (General) ≤ 5 µA
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Conductor cross section AWG (Protective circuit) 24 ... 12
Voltage protection level Up(line-line) (General) ≤ 68 V (C1 - 1 kV/500 A)
Voltage protection level Up(line-earth) (General) ≤ 700 V (C1 - 1 kV/500 A)
Conductor cross section solid (Protective circuit) 0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General) 10 kA
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 85 °C
Conductor cross section flexible (Protective circuit) 0.2 mm² ... 2.5 mm²
Flammability rating according to UL 94 (Ambient conditions) V-0
Nominal discharge current In(8/20) µs (line-line) (General) 0.5 kA
Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General) typ. 60 MHz
Nominal discharge current In(8/20) µs (line-earth) (General) 5 kA
Pulse discharge current Iimp(10/350) µs (line-earth) (General) 0.5 kA

Descrição do produto

Surge protection consisting of plug-in protection and base element, with integrated status indication for a potential-free 3-wire signal circuit with high rated current, EX e approval for Zone 2, suit
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Detalhes técnicos

Dimensional drawing

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top