Horário de atendimento: Segunda a sexta, das 9h às 18h.
TTC-6P-3-HF-12DC-PT-I - TTC-6P-3-HF-12DC-PT-I 1065313 PHOENIX CONTACT Surge protection, consisting of protective plug and base eleme..
Em estoque Produto em alta

TTC-6P-3-HF-12DC-PT-I

TTC-6P-3-HF-12DC-PT-I 1065313 PHOENIX CONTACT Surge protection, consisting of protective plug and base eleme..

$0.00 USD
4120 em estoque
Especificações principais
: C2
Note: 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Type: DIN rail module, two-section, divisible
Depth: 100 mm (incl. DIN rail 7.5 mm)
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
C2
Note 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Type DIN rail module, two-section, divisible
Depth 100 mm (incl. DIN rail 7.5 mm)
Width 6.2 mm +0.1 mm
Height 105.8 mm
Altitude ≤ 4000 m (amsl)
Product type Surge protection for information technology
Mounting type DIN rail: TH 35 - 7.5 mm
Rated current 600 mA (56 °C)
Product family TERMITRAB complete
Open side panel No
Article revision 04
Housing material PBT
Pollution degree 2
Connection method Push-in connection
Nominal voltage UN 12 V DC
Dimensional drawing
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Insulating material PBT
Resistance per path 1.65 Ω ±20 %
Capacity (Core-Core) typ. 32 pF
Color (Base element) gray (RAL 7042)
Degree of protection IP20
Overvoltage category III
Residual current IPE ≤ 200 µA
Capacity (Core-Earth) typ. 32 pF
Color (Male connector) light gray (RAL 7035)
IEC test classification C1
Standards/specifications IEC 61643-21
Input attenuation aE, sym. typ. 0.3 dB (≤ 8.7 MHz/150 Ω)
Max. required back-up fuse 630 mA (FF)
Conductor cross section AWG 24 ... 12
Input attenuation aE, asym. typ. 0.3 dB (≤ 10.5 MHz / 150 Ω)
Response time tA(line-line) ≤ 1 ns
Pulse reset time (line-line) ≤ 30 ms
Response time tA(line-earth) ≤ 1 ns
Conductor cross section rigid 0.2 mm² ... 4 mm²
Maximum continuous voltage UC 15 V DC
Pulse reset time (line-earth) ≤ 30 ms
Impulse durability (line-line) C1 - 1 kV / 500 A
Surge protection fault message optical
Ambient temperature (operation) -40 °C ... 85 °C
Impulse durability (line-earth) C1 - 1 kV / 500 A
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Permissible humidity (operation) 5 % ... 95 %
Operating effective current ICat UC ≤ 100 µA
Flammability rating according to UL 94 V-0
Voltage protection level Up(line-line) ≤ 145 V (C1 - 1 kV / 500 A)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Voltage protection level Up(line-earth) ≤ 80 V (C1 - 1 kV / 500 A)
Total discharge current Itotal(8/20) µs 10 kA
Voltage protection level Upstatic (line-line) ≤ 40 V (C1 - 1 kV / 500 A)
Voltage protection level Upstatic (line-earth) ≤ 40 V (C1 - 1 kV / 500 A)
Max. total discharge current Itotal max(8/20) µs 20 kA (1x)
Nominal discharge current In(8/20) µs (line-line) 5 kA
Cut-off frequency fg (3 dB), sym. in 150 Ω system typ. 60 MHz
Nominal discharge current In(8/20) µs (line-ground) 5 kA
Pulse discharge current Iimp(10/350) µs (line-line) 0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth) 0.5 kA
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system typ. 60 MHz

Descrição do produto

Surge protection, consisting of protective plug and base element, with integrated status indicator for three signal wires with common reference potential. For HF applications and telecommunications in
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top