Horário de atendimento: Segunda a sexta, das 9h às 18h.
VAL-MS 350VF/2+0-FM - VAL-MS 350VF/2+0-FM 2907903 PHOENIX CONTACT Type 2 surge arrester
Em estoque Produto em alta

VAL-MS 350VF/2+0-FM

VAL-MS 350VF/2+0-FM 2907903 PHOENIX CONTACT Type 2 surge arrester

$0.00 USD
3176 em estoque
Especificações principais
GTIN: 4055626257310
Note: Made to Order (non-returnable)
Orderkey: 2907903
(General): T2
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
GTIN 4055626257310
Note Made to Order (non-returnable)
Orderkey 2907903
(General) T2
Depth (Note) 65.7 mm (incl. DIN rail 7.5 mm)
Packing unit 1 pc
Width (Note) 35.6 mm
Height (Note) 97 mm
(NEMA / UL data) EN 61643-11 2012
Country of origin US (United States)
EN type (General) T2
Custom tariff number 85363030
(Ambient conditions) DIN EN 61643-11
(Protective circuit) 10 ... 2 (UL)
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Horizontal pitch (Note) 2 Div.
Type (Ambient conditions) DIN rail module, two-section, divisible
Color (Ambient conditions) black
Response time tA (General) ≤ 100 ns
(Remote indication contact) EN 61643-11 2012
(Standards and Regulations) For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Nominal voltage UN (General) 240/415 V AC (Wye)
TOV behavior at UT (General)
Nominal frequency fN (General) 50 Hz (60 Hz)
Residual current IPE (General) ≤ 10 µA
Shock (operation) (Dimensions) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Rated load current IL (General) 80 A
(Connection, protective circuit) 30 ... 14 (UL)
Degree of protection (Dimensions) IP20 (only when all terminal points are used)
IEC test classification (General) II
Screw thread (Protective circuit) M5
Mounting type (Ambient conditions) DIN rail: 35 mm
Vibration (operation) (Dimensions) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Insulation resistance Riso (General) > 1 GΩ (100 V DC)
Weight per Piece (excluding packing) 222.220 g
Housing material (Ambient conditions) PA 6.6
Stripping length (Protective circuit) 16 mm
China RoHS (Standards and Regulations) Environmentally Friendly Use Period = 50
Connection method (Protective circuit) Fork-type cable lug
Standards/regulations (NEMA / UL data) IEC 61643-11 2011
Standby power consumption PC (General) ≤ 4 mVA
Tightening torque (Protective circuit) 4.5 Nm
Trade restriction (Key Commercial Data) The products are offered exclusively for export outside the EU and the European Economic Area.
Direction of action (Ambient conditions) 2L-PEN
Number of positions (Ambient conditions) 2
Connection technology (Protective circuit) Biconnect terminal block
Voltage protection level Up(L-N) (General) ≤ 1.5 kV
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC power supply system (Ambient conditions) TN-C
Short-circuit current rating ISCCR (General) 25 kA
Max. backup fuse with branch wiring (General) 125 A AC (gG)
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Screw thread (Connection, protective circuit) M2
Max. discharge current Imax(8/20) µs (General) 20 kA
Conductor cross section AWG (Protective circuit) 15 ... 2
Connection name (Connection, protective circuit) Remote fault indicator contact
Nominal discharge current In(8/20) µs (General) 10 kA
Standards/regulations (Remote indication contact) IEC 61643-11 2011
Stripping length (Connection, protective circuit) 7 mm
Connection method (Connection, protective circuit) Screw connection
Tightening torque (Connection, protective circuit) 0.25 Nm
Surge protection fault message (Ambient conditions) Optical, remote indicator contact
Switching function (Connection, protective circuit) PDT contact
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Max. backup fuse with V-type through wiring (General) 80 A AC (gG)
Conductor cross section solid max. (Protective circuit) 35 mm²
Conductor cross section solid min. (Protective circuit) 1.5 mm²
Maximum continuous operating voltage UC(L-PEN) (General) 350 V AC
Conductor cross section flexible max. (Protective circuit) 25 mm²
Conductor cross section flexible min. (Protective circuit) 1.5 mm²
Flammability rating according to UL 94 (Ambient conditions) V-0
Conductor cross section AWG (Connection, protective circuit) 28 ... 16
Nominal discharge current In(L-L) (Standards and Regulations) 10 kA
Voltage protection rating VPR (L-L) (Standards and Regulations) 1.8 kV
Conductor cross section solid max. (Connection, protective circuit) 1.5 mm²
Conductor cross section solid min. (Connection, protective circuit) 0.14 mm²
Standards for cearances and creepage distances (Ambient conditions) IEC 60664-1
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-PE) (General) ≤ 1.5 kV
Conductor cross section flexible max. (Connection, protective circuit) 1.5 mm²
Conductor cross section flexible min. (Connection, protective circuit) 0.14 mm²
Maximum continuous operating voltage MCOV (L-L) (Standards and Regulations) 700 V AC
Maximum continuous operating voltage MCOV (L-N) (Standards and Regulations) 350 V AC

Descrição do produto

More details
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top