VAL-MS-T1/T2 335/12.5 ST - VAL-MS-T1/T2 335/12.5 ST 2800190 PHOENIX CONTACT Type 1/2 surge protection plug
Em estoque Produto em alta

VAL-MS-T1/T2 335/12.5 ST

VAL-MS-T1/T2 335/12.5 ST 2800190 PHOENIX CONTACT Type 1/2 surge protection plug

$0.00 USD
4942 em estoque
Especificações principais
: T1 / T2
Note: 2011
Type: DIN rail module, two-section, divisible
Color: black (RAL 9005)
Informações do fornecedor
Produtos: 0
Geralmente enviado em 2 a 3 dias úteis.
Qualidade garantida
Envio rápido
Suporte técnico

Especificações técnicas

Parâmetro Valor
T1 / T2
Note 2011
Type DIN rail module, two-section, divisible
Color black (RAL 9005)
Depth 67.3 mm
Width 17.7 mm
Height 47 mm
EN type T1 / T2
Altitude ≤ 2000 m (amsl)
SPD Type 4CA
Product type Replacement plug
Mounting type on base element
Material group I
Product family VALVETRAB MS
Nominal voltage 240 V AC
Article revision 07
Horizontal pitch 1 Div.
Housing material PA 6.6
Pollution degree 2
Response time tA ≤ 25 ns
Connection method pluggable
Nominal frequency 50/60 Hz
Shock (operation) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Mode of protection L-N
Nominal voltage UN 240/415 V AC (TN-C, TN-S)
TOV behavior at UT 415 V AC (5 s / withstand mode)
Dimensional drawing
Direction of action L-N / L-PEN
Insulating material PA 6.6/PBT
Number of positions 1
Degree of protection IP20
Nominal frequency fN 50 Hz (60 Hz)
Overvoltage category III
Residual current IPE ≤ 800 µA
CTI value of material 600
Residual voltage Ures ≤ 1.2 kV (at In)
Vibration (operation) 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
IEC power supply system TN-C
IEC test classification I / II
Standards/specifications IEC 61643-11
Power distribution system Single phase
Voltage protection level Up ≤ 1.2 kV
Standby power consumption PC ≤ 270 mVA
Maximum continuous voltage UC 335 V AC
Surge protection fault message optical
Ambient temperature (operation) -40 °C ... 80 °C
Permissible humidity (operation) 5 % ... 95 %
Nominal discharge current In(L-N) 20 kA
Short-circuit current rating ISCCR 25 kA
Max. backup fuse with branch wiring 160 A (gG)
Measured limiting voltage MLV (L-N) 2630 V
Flammability rating according to UL 94 V-0
Nominal discharge current In(8/20) µs 12.5 kA
Ambient temperature (storage/transport) -40 °C ... 80 °C
Maximum discharge current Imax(8/20) µs 50 kA
Impulse discharge current (10/350) µs, charge 6.25 As
Maximum continuous operating voltage MCOV (L-N) 335 V AC
Impulse discharge current (10/350) µs, peak value limp 12.5 kA
Impulse discharge current (10/350) µs, specific energy 39 kJ/Ω

Descrição do produto

Replacement L-N connector for lightning current and plug-in surge discharger VAL-MS-T1/T2 335/12.5.
Principais características
  • Qualidade de nível industrial
  • Em conformidade com a RoHS
  • Certificado CE
  • Garantia de 1 ano

Documentos do produto

Ficha de dados

Especificações técnicas e dados de desempenho

Manual do Usuário

Guia de instalação e operação

Top